logo
>
뉴스
> 회사 뉴스 Fault detection of 10kV cable intermediate joints

Fault detection of 10kV cable intermediate joints

2026-01-21

에 대한 최신 회사 뉴스 Fault detection of 10kV cable intermediate joints

In the intricate network of underground cables beneath the city, accurate fault location means faster restoration of power supply. Recently, we completed a 10kV cable fault detection project, where the fault was located at a hidden intermediate joint.

에 대한 최신 회사 뉴스 Fault detection of 10kV cable intermediate joints  0

End positions The starting point is at the distribution cabinet, and the ending point is at the substation.
On-site situation

The route is clear, following the drainage ditch along the edge of the road.

Insulation resistance The three-phase resistance to ground is low.
Using the instrument

1. XHGG502 Cable Fault Tester

2. XHMR-5kV Insulation Resistance Tester

3. XHHV535-4Z Rod-type High-Voltage Pulse Generator

The three phases of the cable were tested using the 5kV range of the XHMR-5kV insulation resistance tester: the resistance between phase A and ground was approximately 1.2 MΩ, the resistance between phase B and ground was 0.5 MΩ, and the insulation of phase C was normal. Based on this, a fault was determined in phases A and B.

We then used the low-voltage pulse method of the XHGG502 cable fault tester to test the cable. The test results showed that the total length of the cable was approximately 2700.2 meters.

에 대한 최신 회사 뉴스 Fault detection of 10kV cable intermediate joints  1

To determine the location of the cable fault, the waveform was acquired using the high-voltage flashover method of the XHGG502 cable fault tester, which indicated that the fault point was approximately 2000.5 meters from the testing end.

에 대한 최신 회사 뉴스 Fault detection of 10kV cable intermediate joints  2

Using the XHHV535-4Z high-voltage pulse generator, phase B was energized. Initially, the voltage was increased to 20kV without breakdown, but when the voltage reached 22kV, discharge occurred at the fault point.

Because the cable was laid in a trench, the discharge sound could be heard at the manhole cover approximately 2000m away. After descending into the manhole for confirmation, the fault point was identified as a joint failure. Since the insulation of phase A was also low, high voltage was applied to phase A for further testing, and the same joint discharged again, indicating that the fault points of both phases were in the same location.

에 대한 최신 회사 뉴스 Fault detection of 10kV cable intermediate joints  3

In this test, waveform analysis using the high-voltage flashover method presented some difficulties. Interference was present at the site, requiring the identification of periodic discharge signals from the later part of the waveform. This reminds us that:

Waveform analysis requires practical experience.

On-site interference needs to be appropriately handled.

Using multiple methods in combination can improve localization accuracy.